UPS shutdown with NUT over SNMP – Part 2: TrueNAS SCALE

This is the second half of a two-host setup on one shared UPS (APC Smart-UPS SMT1500RMI2U with an AP9630 network card). Part 1 explains the design and the Proxmox side. In short:

  • Every host polls the UPS card directly over SNMP and shuts itself down. No NUT master that everyone depends on.
  • Proxmox goes down at 50%, TrueNAS at 40%. The VMs that write to the NAS are stopped before the NAS itself shuts down.
  • A read-only SNMP community means no host can cut power to the shared UPS.

Tested on TrueNAS SCALE 24.10 (Electric Eel), NUT 2.8.0. Everything here is done in the web UI, no shell editing needed.

1. Prerequisite: SNMP on the card

SNMPv1 has to be enabled on the AP9630 with a read-only community (public). See Part 1 for the steps. In these examples the card is at 192.168.1.50.

2. Configure the UPS service

System → Services → UPS, click the pencil icon to edit:

Field Value Why
Identifier e.g. smt1500 Name of the UPS in NUT (used later with upsc)
UPS Mode Master TrueNAS talks to the card itself; it isn’t a client of another NUT server
Driver APC ups 3 (various) AP9630 SNMP monitoring card (snmp-ups) There’s no bare “snmp-ups” entry; this preset is snmp-ups with the AP9630 mapping
Port or Hostname 192.168.1.50 The card’s IP. Not the default 3493!
Monitor User / Password leave as is Only used internally between upsd and upsmon
Remote Monitor unchecked TrueNAS only watches the card; it doesn’t serve other machines
Shutdown Mode UPS reaches low battery Works together with the override below
Shutdown Timer 30 Grace period in seconds after low battery
Power Off UPS unchecked The UPS is shared; TrueNAS must never switch it off

The classic trap is Port or Hostname. For USB/serial drivers this field holds a device path; for snmp-ups it’s the SNMP target. The preset value 3493 is NUT’s own TCP port and doesn’t belong here. With it the driver looks for an SNMP agent at “3493” and finds nothing.

Auxiliary Parameters (ups.conf)

  • The first two lines tell the driver how to talk SNMP to the card.
  • mibs = apcc is usually already covered by the AP9630 preset, but setting it explicitly does no harm. Add it at the latest if the connection works but the values come back empty.
  • override.battery.charge.low = 40 plus ignorelb make NUT raise low-battery itself at 40%, instead of waiting for the UPS’s own (much later) flag. This is the TrueNAS threshold; Proxmox has 50.

Save, set the service to Running and tick Start Automatically.

3. Verify

In the TrueNAS shell (System → Shell):

If you get a live percentage, TrueNAS is talking to the card. A timeout almost always means: wrong IP in the Port field (still 3493?), routing/VLAN, or SNMPv1 not enabled on the card.

Side note: Reports → UPS may stay empty for a while. That says nothing about whether the shutdown works; upsc is the reliable check.

4. Notifications

Don’t hand-edit upsmon.conf on TrueNAS. The UPS service is managed by the middleware and the files get regenerated on every service restart or update. Use TrueNAS’s own Alert Settings instead (System → Alert Settings). They fire on UPS events natively and survive updates. Email works out of the box; there are also services for Slack, Telegram and Mattermost, among others.

Since both hosts sit on the same UPS, the Proxmox notifier from Part 1 already reports the power cut itself. On TrueNAS the useful extra signal is mainly “TrueNAS is at 40% and shutting down now”.

Pitfalls

  • Port field left at 3493: the most common mistake. It has to be the card’s IP.
  • Power Off UPS enabled: on a shared UPS, that would cut power to everything else.
  • Thresholds the wrong way round: TrueNAS has to go down after the hosts that write to it, so give it the lower percentage.
  • Hand edits in /etc/nut: overwritten on the next restart. Everything belongs in the UI fields and the Auxiliary Parameters.
  • BIOS: enable “power on after AC loss”, or the NAS stays off when the power comes back.

Testing

As in Part 1: in a maintenance window, pull the UPS’s mains plug (or simulate a power failure from the card) and watch the order. Proxmox goes down at 50% while TrueNAS keeps serving its shares, and TrueNAS follows at 40%. That’s the only way to know the shutdown really works, not just that the config looks right.